Parameters |
Unit |
KG30AS |
|
---|---|---|---|
kVA rating at 0.8pf |
kVA(kW) |
30(24) |
|
Voltage |
V |
415 |
|
Frequency |
Hz |
50 |
|
Overall Dimensions with Canopy |
mm(L×B×H) |
3130×1100×1680 |
|
Dry Weight of Genset with canopy |
Kg |
1440 |
|
Electrical Starting System |
|
12 |
|
Battery Capacity |
Ah |
100 |
|
Dg Self Noise Level as per CPCB Norms |
dB(A) |
<75 |
Parameters |
Unit |
HA 494 |
---|---|---|
Rated Output(Prime Continuous Rating)As per ISO 3046 |
kW(hp) |
31.6(43) |
NO. of cylinder |
Number |
4 |
Bore x stroke |
Mm |
100×120 |
Aspiration |
NA/T/TA |
NA |
Governing |
|
Class A2 |
Break mean effective Pressure |
Kg/cm² |
6.8 |
*SFC at 75% load |
Gms/hp-hr |
159 |
*SFC at 100% load |
Gms/hp-hr |
163 |
Lube oil consumption |
Lts/hr |
<0.3% of SFC |
Lube oil change period |
Hrs |
500 |
Lube oil sump capacity |
Ltrs |
11 |
Parameters |
Unit |
KG184C |
---|---|---|
Specifications |
% |
30 kVA |
Insulation Class |
|
H |
Time permitted to build up rated voltage at rated RPM |
Seconds |
< 5 |
Permissible voltage dip @ Full load 0.8pf lag |
% |
<18 |
Alternator efficiency at 100% load |
% |
89.0 |
Alternator efficiency at 100% load |
% |
90.5 |