Prime rating at rated rpm (as per ISO8528) |
kVA |
400 HD |
|
---|---|---|---|
Kw |
320 |
||
Genset Model |
|
KG1-400WS |
|
Frequency |
HZ |
50 |
|
Power factor |
Lagging |
0.8 |
|
Voltage |
V |
415(3Ø ) |
|
Governing class (As per ISO 8528 part-V) |
|
G3 |
|
Noise level |
dBA |
<75 |
|
Fuel Consumption* |
At 100% load |
Ltrs/Hr |
86.9 |
At 75% load |
65.1 |
||
At 50% load |
46 |
||
Fuel tank capacity |
Ltrs |
850 |
|
Overall dimensions of genset (LxWxH)^ |
mm |
5375x2000x2408 |
|
Dry Weight of genset with canopy (approx..)^ |
kg |
6050 |
|
Wet weight of genset with canopy(approx...)^ |
kg |
6800 |
|
Height including Silencer |
kg |
2943 |
|
Electrical Battery starting voltage |
Volts-DC |
24 |
Engine Model |
|
DV8TA G3 |
---|---|---|
Rated output(prime Continuous rating as per ISO 8528-1) |
Kw |
360 |
Hp |
490 |
|
NO. of cylinder |
Number |
8 |
Cubic capacity 2 |
Ltrs |
15.92 |
Bore x stroke |
Mm |
130x150 |
Rated speed |
RPM |
1500 |
Aspiration |
NA/TC/TA |
TA |
Lube Oil change period |
Hrs |
500 |
Lube oil sump capacity Max |
Ltrs |
41 |
Coolant capacity |
Ltrs |
115 |
Insulation Class |
|
Class H |
---|---|---|
Ingression protections |
|
IP 23 |
Altemator Efficiency (at 100% load) 0.8pf** |
% |
93.4 |
Altemator Efficiency (at 75% load) 0.8pf** |
% |
94.0 |
Permissiable Voltage Dip at full load 0.8 pf lag |
Sec |
≤20% |
Time to build up rated voltage at rated RPM |
|
< 1 sec provided engine reach the rated speed |
Short circuit Ratio |
|
0.422 |
Short circuit with stand time |
Sec |
3 Times rated current for 10 sec |
Overload with stand capacity |
% |
10% overload for one hours once in 12 hours |